3.2. Sensor Specifications Setting
3.2. Sensor Specifications Setting
1. Access Path
- Accessible only with the engineer or high mode
- F2.System → 3: Robot Parameters → 12: System Maintenance → 4: Vacuum Robot Sensor Setting
2. Settings Screen
Figure3.2 Sensor Setting Dialog
3. Descriptions and Setting Ranges of Items
1Quantity of temperature sensors
è Setting range: 0–8
2Quantity of fiber sensors
è Setting range: 0–8
3Quantity of flow sensors
è Setting range: 0–4
4Upper/lower limits of temperature sensors
- Depends on the type of temperature sensor
Table 3‑1 Ranges by Types of Temperature Sensors
Type of Temperature Sensor | Temperature Range (°C) |
K, J | -100°C–500°C |
T | -100°C–400°C |
R | 0°C–1500°C |
5Setting range and sensing mode of fiber sensor
- Depending on sensing modes
Table 3‑2 Ranges by Types of Fiber Sensors
Sensing Mode | Description | Setting Range |
1 | High-Speed(H-SP) | 50–4,000 |
2 | Fast (FAST) | 50–4,000 |
3 | Reduce | Not used |
4 | Standard (STD) | 50–4,000 |
5 | Standard Fine | Not used |
6 | Long (LONG) | 50–8,000 |
7 | Ultralong (U-LG) | 50–9,999 |
8 | Hyper (HYPR) | 50–9,999 |
⑥ Upper/lower limits of flow sensors
è Setting range: -1,100–1,100 (l/min)