3.4. Setting – Automatic Grease Injector

3.4. Setting – Automatic Grease Injector

 

A.   Station number setting

Hi-LUB setting: 03

Press the Up Key and Down Key for 3 seconds on the “DC” of the front panel display in the initial status. If the mode changes to the ID window, set the station number and then press the Run key (Enter) for the setting.

 

 - Set in a way to ensure that there should be no station with the same station number on the network.  

- There is no need to perform any other settings separately other than the station number in the injector.  

- Possible to perform the setting from Number 00 to Number 63

 

B.   Status check

The status of the injector front display when the I/O communication with the master is normal.

 

- DC (Disconnect): To be displayed when connection to the DeviceNet is lost when the injector is powered on

- Cn (Connect): To be displayed when connection to DeviceNet is made (The dot next to the Cn mark blinks for the purpose of checking the connection.)

- Lo (Low Grease): Grease filling alarm; the motor will stop after the alarm occurs 10 times (empty signal output).

- AL (Overload): The alarm will occur when an overload occurs. The number of the blocked ports will be displayed. (Example: If P1 is displayed, it means that #1 and #7 are blocked.)

- Display of the icon of rotation: Grease lubrication indication (The motor is rotating.)

 

                                                                                                            

C.   Fixed items in addition to the station number

- Communication speed: Auto (125K, 250K, and 500K all can be detected)

- Input Word: 2 Word (4Byte)

- Output Word: 2 Word (4Byte)