4.2.1. SP Relay
4.2.1. SP Relay
Relay No. | Description | Others |
SP01 | Always On relay | Controller states |
SP02 | Always Off relay | |
SP03 | Relay that only goes On for scan of operation start | Internal timer |
SP04 | 0.1 second clock ( 0.05 second On → 0.05 second Off) | |
SP05 | 0.2 second clock ( 0.1 second On → 0.1 second Off ) | |
SP06 | 1 second clock ( 0.5 second On → 0.5 second Off ) | |
SP07 | On when conversion of BCD operation is not valid | When TOD or FRD is executed. |
SP08 | On when “carry” exist among the operation result | When arithmetic command is executed |
SP09 | 2 second clock ( 1 second On → 1 second Off ) | Internal timer |
SP10 | 4 second clock ( 2 second On → 2 second Off ) | |
SP11 | If On, direct output to Y relay from application (HRBasic, assignment) except PLC is allowed. |
|
SP12 | On when Label is not constant |
|
SP13 | On when quantity of Label is more than 100. |
|
SP14 | On when Label is duplicated |
|
SP15 | On when Label is less than 0 or there is no Label no. to Jump |
|
SP16 | For Modbus Test purpose in Simulation status |
|
SP17 | On when Scan Time exceeds 5 second (In this case, commands that listed after 5 seconds will not be executed). |
|
SP18 | On when a Sub-ladder that is summoned by Call does not exist. |
|
SP19 | 0 = Embedded DeviceNet master error/warning activated (default) 1 = Embedded DeviceNet master error/warning skipped | Support for the version V40.06-00 and up |
SP20 | 0 = FBI communication channel error/warning activated (default) 1 = FBI communication channel error/warning skipped | |
SP21 | 0 = FB3 communication channel error/warning activated (default) 1 = FB3 communication channel error/warning skipped | |
SP22 | 0 = FB5 communication channel error/warning activated (default) 1 = FB5 communication channel error/warning skipped | |
SP23~SP128 | Reserved |
|