4.2.1. SP Relay

4.2.1. SP Relay

 

Relay No.

Description

Others

SP01

Always On relay

Controller states

SP02

Always Off relay

SP03

Relay that only goes On for scan of operation start

Internal timer

SP04

0.1 second clock ( 0.05 second On → 0.05 second Off)

SP05

0.2 second clock ( 0.1 second On → 0.1 second Off )

SP06

1 second clock ( 0.5 second On → 0.5 second Off )

SP07

On when conversion of BCD operation is not valid

When TOD or FRD is executed.

SP08

On when “carry” exist among the operation result

When arithmetic command is executed

SP09

2 second clock ( 1 second On → 1 second Off )

Internal timer

SP10

4 second clock ( 2 second On → 2 second Off )

SP11

If On, direct output to Y relay from application (HRBasic, assignment) except PLC is allowed.

 

SP12

On when Label is not constant

 

SP13

On when quantity of Label is more than 100.

 

SP14

On when Label is duplicated

 

SP15

On when Label is less than 0 or there is no Label no. to Jump

 

SP16

For Modbus Test purpose in Simulation status

 

SP17

On when Scan Time exceeds 5 second

(In this case, commands that listed after 5 seconds will not be executed).

 

SP18

On when a Sub-ladder that is summoned by Call does not exist.

 

SP19

0 = Embedded DeviceNet master error/warning activated (default)

1 = Embedded DeviceNet master error/warning skipped

Support for the version V40.06-00 and up

SP20

0 = FBI communication channel error/warning activated (default)

1 = FBI communication channel error/warning skipped

SP21

0 = FB3 communication channel error/warning activated (default)

1 = FB3 communication channel error/warning skipped

SP22

0 = FB5 communication channel error/warning activated (default)

1 = FB5 communication channel error/warning skipped

SP23~SP128

Reserved