5.1. Error

5.1. Error

 

Code

E32752

“Use data input signal for sensing” is disabled.

Detail

The “Data input setting for sensing” of the arc application setting is disabled.

Action

Among the arc welding entries of application parameter, enable the “Data input setting for sensing.”

 

Code

E32753

“Sensing data type” is “Analog input” and the analog voltage input port is 0.

Detail

In the “Arc welding sensing input data setting,” sensing data type is set to analog input but the port is set to 0.

Action

Set the current sensor input port of the analog input to one where the sensor signal is input.

 

Code

E32754

“Sensing data type” is “Digital input,” and the current sensor digital signal input port is 0.

Detail

In the “Arc welding sensing input data setting” of the arc application setting, the sensing data type is set to digital input but the port no. 0 is set.

Action

Among the arc welding entries of the application parameter, set the digital input entry of the “Data input setting for sensing” according to the system.

 

Code

E32755

The detected initial sensing value is too low.

Detail

Arc sensing input data is too low to perform normal sensing.

Action

1)     Check the state of the sensor and sensor signal line connection.

2)     Check if the voltage detected with the sensor is within a good range using another equipment.

3)     Check if the sensor port and range settings are correct.

 

Code

E32756

Arc sensing current exceeded the normal range above the abnormality determination time.

Detail

Arc sensing input data is unstable so it exceeded the normal range above the abnormality determination time.

Action

1)     Check if the sensing data has been correctly inputted during welding.

2)     If the sensing data is correct, set a large abnormality determination margin and time.

 

Code

E32757

Arc sensing error (exceeded left/right sensing range)

Detail

This error will be occurred when the calculated side tracking distance cannot be catched up for a certain cycle.

Action

Adjust the sensing sensitivity, maximum compensation distance per second, and welding line following gain.

 

Code

E32758

Arc sensing error (upper and lower sensing ranges exceeded)

Detail

This error will be occurred when the calculated height tracking distance cannot be catched up for a certain cycle.

Action

Adjust the sensing sensitivity, maximum compensation distance per second, and welding line following gain.

 

Code

E32759

Abnormal cut-off frequency is entered during filtering

Detail

The cut-off frequency entered for the filtering processing is an abnormal value

Action

1)     Back up all the files in the controller and send them to us.

 

Code

E32760

Abnormal sampling time is entered during filtering

Detail

The distance compensated in the up or down direction exceeded the up / down trajectory deviation limit distance.

Action

1)     Check if the workpiece position is normal.

2)     If the work position is normal, check if the arc sensing trajectory deviates from the welding line.

3)     If there is a deviation from the welding line, check if the arc sensing parameters (data delay time, maximum compensation distance per second, etc.) are normal.

4)    If the arc sensing parameter is normal, check if the data input for sensing is normal.

5)     If there is no problem with the above items, increase the left / right trajectory deviation limit distance.