4.1. Controller Side Error Message

4.1. Controller Side Error Message

 

[Table 4-1] shows the list of warning messages and troubleshooting methods that can be displayed on the teach pendant of the controller while using the Fieldbus.

 

Table 41 Warning Message and Troubleshooting Method on Controller Side

Warning message

Troubleshooting method

W0011

Fieldbus network connection error

Check whether the Fieldbus cable is correctly installed and whether there isn’t any issue with the connection.

W0012

Fieldbus IDLE condition (PLC STOP)

Fieldbus function can only operate when the PLC with Fieldbus master installed is in Run Mode. Check this.

Also please check if the communication speed is matched up with masters.

W0013

Fieldbus module is not detected.

Check whether the Bd57x CC-Link module is correctly connected and whether 5V of power is supplied.

W0014

Fieldbus setting error.

Check whether the dip switch of the Fieldbus module is correctly set up.

W0027

The field bus master setting is CC-Link v1.0

On CC-Link master, Hi5 Controller is incorrectly set as CC-Link v1.0 slave. Please set it as v2.0 slave.

 

Because the Hi5 Controller periodically retries for normal communication, the Fieldbus communication may automatically be reconnected once the issue is resolved. Turn off and on both of PLC and Controller, if the connection issue is not resolved after the change of setting.