1.3.1. Adjustment of Power System

1.3.1. Adjustment of Power System

 

In case of power system errors or power change, take a measurement of each power voltage, and adjust any voltage below the standard (use a digital voltmeter for measurement).

 

Table 17 power standard value

Power

Measuring Location

Standard

Adjustment

Primary Power

CB1 input terminal

AC220V ± 10%

The first tap of the transformer TR1 is defined as AC220V

R6,S6,T6

Servo AMOP R, S, T

AC220V ± 10%

Check the CB1 input voltage (AC220V).

B2-C2

TB1 B2-C2

AC220V ± 10%

Transformer TR1 second tap change

P1-M1

SR1  +24V-G2

DC24V ± 2.0V

(Note 1)

P5-M0

SR1  +5V-G1

DC5.1V ± 0.1V

SR1 volume resistivity

P15-M0

SR1  +15V-G1

DC15V ± 0.5V

(Note 1)

N15-M0

SR1  -15V-G1

DC-15V ± 0.5V

(Note 1)

P5E-M5E

SR1  +5V-GND

DC5.4V ± 0.1V

SR1 volume resistivity (Note 2)

Robot external wiring terminal and connector pins P5E-M5E

DC5.1V ± 0.1V

SR1 volume resistivity (Note 2)

 

(Note 1) Replace the SR1 if it is not within the standard.

(Note 2) First, check the standard in the measuring location, and then make a measurement in the nearest terminal stand from robot encoder and between connector Pins. Here, the standard must be DC5.1V±0.1V.