6.3.1. Adjustment of Power System

6.3.1. Adjustment of Power System

 

In case of power system errors or power change, take a measurement of each power voltage, and adjust any voltage below the standard (use a digital voltmeter for measurement).

 

Table 66 Power Standard

Power

Measuring Location

Standard

Adjustment

Primary Power

CB1 input terminal

AC220V ± 10%

Define the primary tab of transformer TR1 as AC220V

R6,S6,T6

Servo AMP R, S, T

AC220V ± 10%

Check the input voltage of CB1 - AC220V

B2-C2

TB1 B2-C2

AC220V ± 10%

Secondary Tab turnover of transformer TR1

P1-M1

SR1 +24V-G2

DC24V ± 2.0V

(Note 1)

P5-M0

SR1 +5V-G1

DC5.1V ± 0.1V

Volume resistance in SR1

P15-M0

SR1 +15V-G1

DC15V ± 0.5V

(Note 1)

N15-M0

SR1 -15V-G1

DC-15V ± 0.5V

(Note 1)

P5E-M5E

SR1 +5V-GND

DC5.4V ± 0.1V

Volume resistance in SR1 (Note 2)

Terminal block for Robot external wiring Connectors Pin P5E-M5E

DC5.1V ± 0.1V

Volume resistance in SR1 (Note 2)

 

(Note 1) Replace the SR1 if it is not within the standard.

(Note 2) First, check the standard in the measuring location, and then make a measurement in the nearest terminal stand from robot encoder and between connector Pins. Here, the standard must be DC5.1V±0.1V.